Rockwell Automation RECOMM-ENET EtherNet/IP Communications Module User Manual
Page 94

8-4
EtherNet/IP Communications Module
8.1.3 NET A Status Indicator
Table 8.4 – NET A Status Indicator: State Definitions
Status
Cause
Corrective Action
Off
The module and/or
network is not
powered, the
module is not
connected properly
to the network, or
the module needs
an IP address.
•
Securely connect the module to
the drive using the Internal
Interface cable and to the
network using an Ethernet
cable.
•
Correctly connect the Ethernet
cable to the Ethernet connector.
•
Set a unique IP address using a
BOOTP server or disabling
BOOTP and using parameters.
•
Apply power to the drive and
network.
Solid Red
The module failed
duplicated IP
address detection
test.
•
Configure the module to use a
unique IP address and cycle
power.
Flashing
Red
An EtherNet/IP
connection has
timed out.
•
Place the scanner in RUN
mode, or apply power to the
peer device that will send I/O.
•
Check the amount of traffic on
the network.
Flashing
Red/
Green
The module is
performing a self
test.
•
No action is required.
Flashing
Green
The module is
properly connected
but is not
communicating
with any devices
on the network.
•
Place the controller in RUN, or
apply power to the peer device
that will send I/O.
•
Program a controller or peer
device to recognize and
transmit I/O or make a
messaging connection to the
module.
•
Configure the module for the
program in the controller or the
I/O from the peer device.
Solid
Green
The module is
properly connected
and
communicating
with the network.
•
No action required.