Rockwell Automation RECOMM-ENET EtherNet/IP Communications Module User Manual
Page 38

4-12
EtherNet/IP Communications Module
4.8.2 Configuring the Module to Transmit Peer-to-
Peer Data
To configure an module to transmit Peer-to-Peer data:
Step 1.
Verify that module parameter 51 (Peer Out Enable) is set
to Off (see figure 4.15). This parameter must be Off while
you configure peer output parameters.
Step 2.
Select the source of the data to output to the network in
module parameter 49 (Peer A Output). See figure 4.16.
Step 3.
If desired, select an additional source of the data to output
to the network in module parameter 50 (Peer B Output) as
shown in figure 4.17.
Step 4.
Set module parameters 52 (Peer Out Time) and 53 (Peer
Out Skip) to establish the minimum and maximum
intervals between Peer messages. Because the module
Figure 4.15 – Peer Out Enable Screen on an LCD OIM
Figure 4.16 – Peer A Output Screen on an LCD OIM
Figure 4.17 – Peer B Output Screen on an LCD OIM
Value Setting
0
Off (Default)
1
On
Port 5 Device
RECOMM-ENET
Parameter #: 51
Peer Out Enable
0
Off
Port 5 Device
RECOMM-ENET
Parameter #: 49
Peer A Output
1
Cmd/Ref
Value
Description
0
Off (Default)
1
Logic Command/Reference
2 - 5
Datalink A, B, C, or D Input
6 - 9
Datalink A, B, C, or D Output
Port 5 Device
RECOMM-ENET
Parameter #: 50
Peer B Output
2
DL A Input
Value
Description
0
Off (Default)
1
Logic Command/Reference
2 - 5
Datalink A, B, C, or D
Input
6 - 9
Datalink A, B, C, or D
Output