Module Parameters

B-11

Sets the percent scale factor for the Reference from the network.

Selects the destination in the drive of the Peer I/O input. The
module receives this data from the network and sends it to the drive.

Important: Changes to these parameters are ignored when module

parameter 47 (Peer Inp Enable) is On.

Important: If the parameter is set to input a logic command,

configure the mask in module parameter 40 (Peer Cmd
Mask) so that the desired bits from the Peer device are
used.

37

Ref Adjust

Range:

0.00 to 200.00 %

Default:

100.00 %

Type:

Read/Write

Reset Required: No

!

ATTENTION: Changes to module parameter 37 (Ref
Adjust) take effective immediately. A drive receiving its
Reference from the module will receive the newly
scaled Reference, resulting in change of speed.
Failure to observe this precaution could result in bodily
injury and/or damage to equipment.

38
39

Peer A Input
Peer B Input

Range:

0 = Off
1 = Cmd/Ref
2 = Datalink A Input
3 = Datalink B Input
4 = Datalink C Input
5 = Datalink D Input

Default:

0 = Off

Type:

Read/Write

Reset Required: No