C.9 dpi fault object – Rockwell Automation RECOMM-ENET EtherNet/IP Communications Module User Manual
Page 161

EtherNet I/P Objects
C-25
C.9 DPI Fault Object
Class Code
Products such as SP600, GV6000 and LiquiFlo 2.0 drives use this
object for faults. Modules use this object for events.
Instances
The number of instances depends on the maximum number of
faults or events supported in the queue. The maximum number of
faults/events can be read in Instance 0, Attribute 2.
Class Attributes
Hexadecimal
Decimal
0x97
151
Instances (Hex)
(Dec)
Device
Example
Description
0x0000-0x3FFF 0-16383
Host
0
Class Attributes (Drive)
0x4000-0x43FF
16384-17407 Module
1
Most Recent Drive Fault
0x4400-0x47FF
17408-18431 DPI Port 1
2
Second Most Recent
Drive Fault
0x4800-0x4BFF 18432-19455 DPI Port 2
...
...
0x4C00-0x4FFF 19456-20479 DPI Port 3
16384
Class Attributes (Module)
0x5000-0x53FF
20480-21503 DPI Port 4
16385
Most Recent Module
Event
0x5400-0x57FF
21504-22527 DPI Port 5
...
...
0x5800-0x5BFF 22528-23551 DPI Port 6
Attribute
ID
Access
Rule
Name
Data Type
Description
1
Get
Class Revision
WORD
Revision of object
2
Get
Number of
Instances
WORD
Maximum number of faults/events
that the device can record in its
queue
3
Set
Fault Command
Write
BYTE
0 = No Operation
1 = Clear Fault/Event
2 = Clear Fault/Event Queue
3 = Reset Device
4
Get
Fault Trip
Instance Read
WORD
Fault that tripped the device. For
modules, this value is always 1
when faulted.