Module Parameters

B-15

Enables or disables the Peer I/O output.

Sets the minimum time that a module will wait when transmitting
data to a peer.

Important: Changes to these parameters are ignored when

parameter 51 (Peer Out Enable) is On.

Sets the maximum time that a module will wait when transmitting
data to a peer. The value of parameter 52 (Peer Out Time) is
multiplied by the value of this parameter to set the time.

Important: Changes to this parameter is ignored when parameter

51 (Peer Out Enable) is On.

51

Peer Out Enable

Range:

0 = Off
1 = On

Default:

0 = Off

Type:

Read/Write

Reset Required: No

52

Peer Out Time

Range:

0.01 to 10.00 sec

Default:

10.00 sec

Type:

Read/Write

Reset Required: No

53

Peer Out Skip

Range:

1 to 16

Default:

1

Type:

Read/Write

Reset Required: No