Rockwell Automation RECOMM-ENET EtherNet/IP Communications Module User Manual
Page 112

Viewing the Module’s Web Pages
9-10
Important:For firmware 2.xxx (and earlier) modules, it is
recommended that Access Control (54) E-mail Config
Bit 1 value be set to “0” (Disabled) after E-mail
Notification has been configured. Otherwise the
configuration can be changed anytime the web page is
accessed with a browser.Forfirmware 3.xxx (and later)
modules, it is recommended that Web Features (56) E-
mail Cfg Bit 0 value be set to “0” (Disabled) after E-mail
Notification has been configured. Otherwise the
configuration can be changed anytime the web page is
accessed with a browser.
An example of an e-mail message automatically sent by the adapter
in response to selected events is shown below.
Note: To stop e-mail messages, do one of the following:
•
Delete all e-mail addresses from the Configure E-mail Notification
web page.
•
Uncheck all of the “Send an e-mail message when ...” boxes.
For firmware 2.xxx (and earlier) modules, disabling the adapter web
pages by using Access Control (54) to set the Web Enable Bit 0
value to “0” (Disabled) will NOT stop the module from sending e-
mail messages.
For firmware 3.xxx (and later) modules, setting the Web Pages
Switch to the “Disable Web” position will NOT stop the module from
sending e-mail messages.
Figure 9.6 – Example of E-mail Message Ssent by Module