beautypg.com

Rockwell Automation 20D PowerFlex 700S and 700H Frame 10...12 Rectifier Module Replacement Kit User Manual

Page 47

background image

47

Publication PFLEX-IN023A-EN-P

Measurement Points for Forward and Reverse Diode Tests Frame 11 Drives

Figure 9 Measurement Points for Forward and Reverse Diode Tests

Series A Rectifier Circuit Board - Rectifier Module Tests

Table E Forward Biased Diode Tests on Rectifier Module(s)

Meter Leads

Nominal meter reading

+

-

L1

DC+

The value should gradually rise to about 0.5V

(1)

(1)

The actual voltage reading may vary depending upon your equipment. If your readings are not near 0.5V, verify
that the actual voltage measured is consistent for the Rectifier module(s) and the Output Power modules.

L2

DC+

L3

DC+

DC-

L1

DC-

L2

DC-

L3

2L1

2L2

2L3

1L1

1L2

1L3

U/T1

V/T2

W/T3

DC-

DC+

Note: 600V ac input, 460A and 502A frame 11
drives only have one rectifier module.