beautypg.com

Rockwell Automation 20D PowerFlex 700S and 700H Frame 10...12 Rectifier Module Replacement Kit User Manual

Page 38

background image

Publication PFLEX-IN023A-EN-P

38

26. Remove the M10 bolts and washers that secure the AC input supply cables

and SCR terminal bus bars to the rectifier module and remove the cables
and bus bars from the rectifier module.

27. Remove the six M10x20 bolts and washers that secure the DC- and DC+

rectifier bus bars to the rectifier module and remove the bus bars.

Important: Do Not reuse the existing DC+ rectifier bus bar.

Remove bolts

17 mm
12 N•m
(106 lb•in)

AC supply cables

Terminal bus bars

Remove bolts

17 mm
12 N•m
(106 lb•in)

Do Not reuse existing DC+ bus bar