Power Module-Dependent Parameter Values

Second Menu General Parameters (USA Defaults)

Parameter

Name

Carrier
Frequency (kHz)

Parameter

No.

P.047

30V2060

4

50V2060

4

75V2060

4

100V2060

4

Note: The drives can use any carrier frequency of 2, 4 or 8 kHz. But when 8 kHz of carrier frequency is used, the drive's rated output current is

automatically limited to 80%.

A

PPENDIX

C

Power Module-Dependent Parameter

Default Values (230 V Series)

Power Module

Second Menu Volts/Hertz Parameters (USA Defaults)

Parameter

Name

Motor Nameplate
Amps

Parameter

No.

H.002

40V2060

97.4

50V2060

125.0

75V2060

170.0

100V2060

224.0

Power Module

Second Menu Vector Parameters (USA Defaults)

Parameter

Name

Motor Nameplate
Amps
Motor Nameplate
RPM
Magnetizing Current
Speed Reg. Prop.
Gain
Speed Reg. Int. Gain
Torque Reg. Prop.
Gain
Torque Reg. Int. Gain
Field Weakening
Start RPM
Motor Top Speed
Flux Current Reg.
Prop. Gain
Flux Current Reg. Int.
Gain
Rotor Time Constant
Motor Nameplate HP
SVC Flux Current
Reg. Gain

Parameter

No.

U.004

U.005

U.006
U.012

U.013
U.014

U.015
U.016

U.017
U.019

U.020

U.021
U.022
U.032

30V2060

71.0

1770

44.0
5.00

5.00
0.40

200.0

1770

1770

0.15

50.0

250

30.0

800

50V2060

125.0

1775

44.0
5.00

5.00
0.40

200.0

1775

1775

0.15

50.0

250

50.0

700

60V2060

130.0

1780

49.0
5.00

5.00
0.40

200.0

1780

1780

0.15

50.0

250

60.0

650

100V2060

177.2

1780

35.0
5.00

5.00
0.40

200.0

1780

1780

0.15

50.0

250

100.0

550

Power Module

40V2060

4

60V2060

4

30V2060

71.0

60V2060

136.0

40V2060

97.4

1775

47.0
5.00

5.00
0.40

200.0

1775

1775

0.15

50.0

250

40.0

750

75V2060

154.0

1780

46.0
5.00

5.00
0.40

200.0

1780

1780

0.15

50.0

250

75.0

600