H.000 motor nameplate base volts, H.001 motor nameplate base frequency – Rockwell Automation GV3000/SE 230VAC 30-100HP GP & Vector Drive V6.04 Start-Up and Reference Manual User Manual
Page 143

4-57
Programming Reference
4.6.3 Second Menu V/Hz Parameter Descriptions (H.000 to H.022)
H.000 Motor Nameplate Base Volts
This parameter
identifies the motor
nominal voltage as it
appears on the motor
nameplate.
Parameter Range:
100 VAC to 345 VAC
Default Setting:
230 VAC
Parameter Type:
Configurable
Refer also to parameters: N/A
H.001 Motor Nameplate Base Frequency
This parameter
configures the V/Hz
ratio.
Parameter Range:
30.0 Hz to 200.0 Hz
Default Setting:
60.0 Hz
Parameter Type:
Configurable
Refer also to parameters: H.003 Torque Boost Voltage
H.018 Volts/Hertz Curve Type
Base frequency is the frequency at which th
e output voltage reaches Motor
Nameplate Voltage (H.000). Below base frequency, the output voltage varies with
output frequency according to the V/Hz adjustment in parameter H.018 (Volts/Hertz
Curve Type). Above base frequency, output voltage is held constant as frequency
increases (constant horsepower range).
The V/Hz ratio is affected by the selection of Volts/Hertz Curve Type in H.018 and
the setting of Torque Boost Voltage in H.003. See figure 4.10.
100
30
H.001
Maximum
V/Hz
Minimum
V/Hz
Motor
Voltage,
(H.000)
(volts)
Output Frequency
(Hz)
Figure 4.10 - Volts/Hertz Ratio