4.6.3 Second Menu V/Hz Parameter Descriptions (H.000 to H.022)

H.000 Motor Nameplate Base Volts

This parameter
identifies the motor
nominal voltage as it
appears on the motor
nameplate.

Parameter Range:

100 VAC to 345 VAC

Default Setting:

230 VAC

Parameter Type:

Configurable

Refer also to parameters: N/A

H.001 Motor Nameplate Base Frequency

This parameter
configures the V/Hz
ratio.

Parameter Range:

30.0 Hz to 200.0 Hz

Default Setting:

60.0 Hz

Parameter Type:

Configurable

Refer also to parameters: H.003 Torque Boost Voltage

H.018 Volts/Hertz Curve Type

Base frequency is the frequency at which th
e output voltage reaches Motor
Nameplate Voltage (H.000). Below base frequency, the output voltage varies with
output frequency according to the V/Hz adjustment in parameter H.018 (Volts/Hertz
Curve Type). Above base frequency, output voltage is held constant as frequency
increases (constant horsepower range).

The V/Hz ratio is affected by the selection of Volts/Hertz Curve Type in H.018 and
the setting of Torque Boost Voltage in H.003. See figure 4.10.

100

30

H.001

Maximum

V/Hz

Minimum

V/Hz

Motor

Voltage,

(H.000)

(volts)

Output Frequency

(Hz)

Figure 4.10 - Volts/Hertz Ratio