4-34

GV3000/SE 230 VAC Drive, Software Reference Version 6.04

Figure 4.6 - Typical Preset Operation

P.031 to P.038 Preset Speed 1 Through Preset Speed 8

(continued)

P.038

P.037

P.036

P.035

P.034

P.033

P.032

P.031
Preset 1
(or TS
Analog in)

Digital In 6
(Term. 19)

Digital In 7
(Term. 18)

Digital In 8
(Term. 17)

Run and Start

Closed

Closed

Closed

Closed

Closed

Closed

Closed

Closed

P.039 Encoder Loss Enable

This parameter
enables the encoder
loss detection
diagnostic.

This diagnostic is
available for flux
vector control (FVC)
only.

Parameter Range:

OFF = Disable encoder loss diagnostic

ON = Enable encoder loss diagnostic

Default Setting:

OFF

Parameter Type:

Tunable

Refer also to parameters: N/A

The encoder loss detection diagnostic is functional only when the drive is operating
as a speed regulator (not as a torque regulator).

When the diagnostic is enabled and feedback from the encoder is not detected, a
drive fault will be logged (EL will be displayed).

If the encoder fails, loss will be detected down to 1 RPM. If only one of the
quadrature feedback wires is disconnected, loss may not be detected below 15
RPM.