4-21

Programming Reference

P.012 Terminal Strip Analog Output Source

(continued)

Figure 4.2 - Analog Output Selection and Scaling

P.013 Output Relay Configuration

This parameter
specifies the type of
status indication
provided by the
output relay contacts
(terminal 28, 29, 30,
and 31 on the drive's
terminal strip).

Parameter Range:

0 = Output relay is energized when one or more

faults (IET) are active.

1 = Output relay is energized to show state of drive

running with 0.5 second delay added between a
start assertion and generation of motor voltage.

2 = Output relay is energized to show state of drive

running but without 0.5 second start delay.

3 = Output relay is energized when network

communication is active.

4 = Output relay is energed when all start

permissive conditions are met.

5 = Output relay is energed when one or more

alarms are active.

Default Setting:

0

Parameter Type:

Configurable

Refer also to parameters: N/A

For example, for an application using an output contactor, you can obtain a 0.5
second delay between a start assertion and the generation of motor voltage by
setting P.013 to 1. The delay will provide time for the contactor to close before
motor voltage is generated.

This parameter has been modified in version 6.04.

10V

20 mA

0V

4 mA

0

0

10V

20 mA

0V

4 mA

– Max Speed
– Top Speed

–200% Torque
–300% Torque

+Max Speed (P.004)
+Top Speed (U.017)

+200% Torque
+300% Torque

P.012 = 0

P.012 = 1

V/Hz
Vector

V/Hz
Vector

V/Hz
Vector

V/Hz
Vector

– Max Speed
– Top Speed

–200% Max Current (2 x P.095)
–300% Torque

+Max Speed (P.004)
+Top Speed (U.017)

+200% Max Currenr (2 x P.095)
+300% Torque

P.012 = 2

P.012 = 3