Rockwell Automation GV3000/SE 230VAC 30-100HP GP & Vector Drive V6.04 Start-Up and Reference Manual User Manual

Page 182

background image

5-4

GV3000/SE 230 VAC Drive, Software Reference Version 6.04

Fault Cause

DC bus voltage too low. Line dip too
long (P.042).

Input rectifier diodes defective.

Communications with the AutoMax
network have been lost.

Drive started but Identification Result =
Zero.

Output phase-to-phase short.

Bus voltage line-to-line.

Ground fault.

Momentary overload.

Bad motor.

Torque boost/ V/Hz too high (V/Hz).

Motor unknown to regulator (V/Hz).

Parameter settings (Vector).

Encoder wired incorrectly, wrong PPR.

Cooling fan failure.

Acceleration time too short.

DC voltage too high.

Deceleration time too short.

Corrective Action

Check input voltage, line fuses.
If necessary, add transformer. Check
value of Ride-Through Time (P.042), Line
Voltage (H.021, U.018).

Check DC Bus voltage. If incorrect,
replace diode set.

Check network cabling from network
master to network option board. Check
that network master is operating
properly.

Reset fault. Perform Identification
Request. Restart drive.

Check isolation between each output line.

Check transistor modules for correct
output. If incorrect, possible board
defect; replace. Possible Hall effect
current sensor defective; replace.

Check isolation between ground and
output terminals. Possible leakage
current sensor defect; replace sensor.

Check for motor overload; reduce load on
motor.

Check motor for correct operation.

Check parameters H.001, H.002, and/or
H.003. Enable Identification Request
(H.020)

Check that regulator was updated with
actual motor characteristics via
Identification Request (H.020).

Check Encoder PPR (U.001), Motor
Poles (U.002), Base Frequency (U.003),
Motor Nameplate Amps (U.004),
Magnetizing Current (U.006), Speed
Regulator Prop. Gain (U.012).

Check encoder wiring. Perform vector
self-tuning.

Check ambient temperature, cooling fan,
minimum clearances around drive.

Increase acceleration time (P.001, P.017,
P.021).

Check parameters H.006, H.007.

Increase deceleration time (P.002, P.018,
P.022).

Fault

Description

Low DC bus voltage

Network comm loss

Identification
Request not yet
performed (V/Hz
only)

Overcurrent (steady
state).
Trips at 137% load
(based on inverter
type current) check
Power Module
rating.
Drive
overtemperature.

Overcurrent (at
acceleration)

Overcurrent (at
DC braking)

Overcurrent (At
deceleration

Code

LU

nCL

nId

OC

OCA

OCb

OCd

Table 5.2 - List of Fault Codes (Continued)