beautypg.com

H.009 avoidance frequency enable – Rockwell Automation GV3000/SE 230VAC 30-100HP GP & Vector Drive V6.04 Start-Up and Reference Manual User Manual

Page 149

background image

4-63

Programming Reference

H.009 Avoidance Frequency Enable

(continued)

Max Hz

AF 3

AF 2

AF 1

Min Hz

Min

Max

Speed Reference

Output
Frequency

Base Frequency

Avoidance
Frequency Band

Figure 4.12 – Avoidance Frequency Band

H.010, H.012, H.014 Avoidance Frequency Midpoint 1, 2, and 3

This parameter
specifies the midpoint
of each avoidance
frequency band
selected in H.011,
H.013, and H.015.

The adjusted values may be in any order. The frequency will not be affected at
normal acceleration or deceleration but will be avoided at continuous output
frequency.

Parameter Range:

0.0 to 200.0 Hz

Default Setting:

0.0

Parameter Type:

Tunable

Refer also to parameters: H.009 Avoidance Frequency Enable

H.011, H.013, H.015 Avoidance Frequency Band 1,

2, and 3