GV3000/SE 230 VAC Drive, Software Reference Version 6.04

P.020 Jog Speed Reference

This parameter is the
speed reference for
the drive when JOG
is selected.

Jog reference is independent of any other speed reference. Unlike the run speed
reference, the jog speed reference cannot be adjusted using the

£

or

¥

keys.

Parameter Range:

Minimum Speed (P.003) to Maximum Speed (P.004)

Default Setting:

5.0 Hz (V/Hz)
150 RPM (vector)

Parameter Type:

Tunable

Refer also to parameters: P.003 Minimum Speed

P.004 Maximum Speed

P.021 Jog Ramp Accel Time

For V/Hz regulation,
this parameter
specifies the amount
of time (seconds) it
takes the motor to
ramp from zero
speed to Maximum
Speed (P.004) when
JOG is selected.

For vector regulation,
this parameter
specifies the amount
of time (seconds) it
takes the motor to
ramp from zero
speed to Motor Top
Speed (U.017) when
JOG is selected.

Parameter Range:

1.0 to 999.9 seconds (V/Hz)
0.1 to 999.9 seconds (vector)

Default Setting:

20.0

Parameter Type:

Tunable

Refer also to parameters: P.004 Maximum Speed

U.017 Motor Top Speed

The time the motor takes to make any speed increase is directly proportional to the
value in this parameter.