4-46

GV3000/SE 230 VAC Drive, Software Reference Version 6.04

P.055 STOP/RESET Key Disable

This parameter
disables the STOP/
RESET key except
from the selected
control source.

Parameter Range:

OFF = Enable the STOP/RESET key regardless of

the control source

ON = Disable the STOP/RESET key except from the

selected control source

Default Setting:

OFF

Parameter Type:

Tunable

Refer also to parameters: P.000 Control Source

ATTENTION: When P.055 is set to ON, the STOP/RESET key is
functional only from the selected control source. As a safety
precaution, Reliance recommends that an emergency stop push button
be located near the drive in an easily accessible location. As a further
safety precaution, the user should post a warning on the drive to alert
personnel that the STOP/RESET key is not functional. Failure to
observe this precaution could result in severe bodily injury or loss of
life.

Table 4.7 details whether the STOP/RESET key is active based on the selected
control source (P.000) and P.055.

Table 4.7 – STOP/RESET Key Status Based on P.000 and P.055

!

Control Source (P.000 =)

Front panel (LOCL)

Terminal strip (rE)

Network/option board (OP)

OIM/CS3000 (SErL)

Front panel (LOCL)

Terminal strip (rE)

Network/option board (OP)

OIM/CS3000 (SErL)

P.055

OFF

OFF

OFF

OFF

ON

ON

ON

ON

Front Panel

STOP/RESET Key

Active

Active

Active

Active

Active

Inactive

Inactive

Inactive

OIM/CS3000

STOP/RESET Key

Active

Active

Active

Active

Inactive

Inactive

Inactive

Active