Programming Reference

P.015 Trim Gain Percentage

This parameter
specifies a
percentage of the
selected trim
reference entering
the speed regulator.

See figure 4.4.

Parameter Range:

–99.9 to +99.9% (1.0 = 1%)

Default Setting:

0.0

Parameter Type:

Tunable

Refer also to parameters: P.014 Trim Reference Source

Draw Gain

Mul

Div

Trim Gain

Mul

Div

P.016

Draw

P.015

Trim

Selected

Speed Ref

To Speed Ref
Limit Block

100

100

+

+

+

Selected

Trim Ref

P.014

Figure 4.4 - Draw and Trim Gain

See Appendix G for the complete block diagram.

P.016 Draw Gain Percentage

This parameter is
used to increase or
decrease the
selected speed
reference to the
speed regulator.

Parameter Range:

–99.9 to +99.9% (1.0 = 1%)

Default Setting:

0.0

Parameter Type:

Tunable

Refer also to parameters: N/A

This parameter allows multiple drive sections with a common line reference, but with
different values for draw gain, to run at different speeds depending on the percent
draw.