Wiring the Regulator Board Terminal Strip

Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)

Terminal

Number

28

29

30

31

Description

Normally-Closed Contact
(Form B)

Normally-Closed Contact
Common (Form B)

Normally-Open Contact
(Form A)

Normally-Open Contact
Common (Form A)

Parameters/Wiring Connections

Both Form A and Form B contacts are rated for 250 VAC/30 VDC at
5 amps resistive or 2 amps inductive load.

The following parameter must be set:

P.013: Output Relay Configuration

Note that depending on the setting of parameter P.013, the
relay coil will energize (the normally-open contact will close and the
normally-closed contact will open). Refer to the GV3000/SE
Software Start-Up and Reference manual for more information.

Wiring the Output Status Relays

28 29 30 31

N.C.

COM

N.O.

COM

USER SUPPLIED

DEVICE

PARAMETER P.013 SELECTS OUTPUT

INDICATION