2 installing fuses for branch circuit protection – Rockwell Automation GV3000/SE AC Drive 30-100HP, 230VAC V6.04 Hardware Ref, Install, Troubleshooting User Manual
Page 44
5-2
GV3000/SE 230 VAC 30-100 HP Drive, Hardware Reference Version 6.04
5.2 Installing Fuses for Branch Circuit Protection
Install the required, user-supplied branch circuit protection fuses according to the
applicable local, national, and international codes (e.g., NEC/CEC). The fuses must
be installed in the line before the drive input terminals. See figures 5.1 and 5.2.
Fuse value selections are provided in table 3.6.
ATTENTION: Most codes require that upstream branch protection be
provided to protect input power wiring. Failure to observe this
precaution could result in severe bodily injury or loss of life.
5.3 Installing a Required External/Separate Input Disconnect
An input disconnect must be installed in the line before the drive input terminals in
accordance with local, national, and international codes (e.g., NEC/CEC). The
disconnect should be sized according to the in-rush current as well as any additional
loads the disconnect might supply. The trip rating for the inrush current (10-12
times full load current) should be coordinated with that of the input isolation
transformer, if used. Refer to section 5.1 for additional information.
GV3000/SE Drive
30 HP
40 HP
50 HP
60 HP
75 HP
100 HP
Line Reactor Inductance (+/–10%)
84
µ
H
66
µ
H
66
µ
H
54
µ
H
42
µ
H
36
µ
H
Table 5.1 - AC Line Reactors
!