2-11

About the Drive

Figure 2.8 - Keypad/Display

2.5 Jumpers on Base Board (PISC-40)

Jumpers JP1 through JP4 on the Base board (PISC-40) are used for selection of
current feedback gain as shown in table 2.2. On the Base board, there is another
jumper, JP6, to be used for selection of ON/OFF level of precharge relay. Table 2.2
also shows the factory settings of these jumpers. For the locations of these jumpers,
see figure 2.9.

Table 2.2 - Settings of Jumpers on Base Board

2.4.6 Keypad/Display

The front panel keypad/display is used to program and operate the GV3000/SE
drive. See figure 2.8. Refer to the GV3000/SE Software Start-Up and Reference
manual for more information.

£

AUTO

MAN

Forward

Reverse

PROGRAM

RUN

JOG

ENTER

STOP

RESET

START

SPEED

VOLTS

AMPS

Hz

Kw

TORQUE

Password

RUNNING

REMOTE

JOG

AUTO

FORWARD

REVERSE

PROGRAM

.

Keypad

Monitor Mode
LEDs

Display

Drive Status LEDs

Start Key

Stop / Reset
Key

Password LED

¥

Jumpers

JP1

(for U-phase)

JP2

(for V-phase)

JP3

(for bus current)

JP4

(for bus current)

JP6

Description

These jumpers are used for selection of
current feedback gain as follows:
A:

for 30 to 50 HP units

B:

for 60 to 100 HP units

This jumper is used for selection of ON/OFF
level of precharge relay as follows:
A: ON at 175 V, OFF at 155 V
B: ON at 220 V, OFF at 200 V

Factory Setting

For 30 to 50 HP units:
:

A

For 60 to 100 HP
units: B

Set to A position