2-11
About the Drive
Figure 2.8 - Keypad/Display
2.5 Jumpers on Base Board (PISC-40)
Jumpers JP1 through JP4 on the Base board (PISC-40) are used for selection of
current feedback gain as shown in table 2.2. On the Base board, there is another
jumper, JP6, to be used for selection of ON/OFF level of precharge relay. Table 2.2
also shows the factory settings of these jumpers. For the locations of these jumpers,
see figure 2.9.
Table 2.2 - Settings of Jumpers on Base Board
2.4.6 Keypad/Display
The front panel keypad/display is used to program and operate the GV3000/SE
drive. See figure 2.8. Refer to the GV3000/SE Software Start-Up and Reference
manual for more information.
£
AUTO
MAN
Forward
Reverse
PROGRAM
RUN
JOG
ENTER
STOP
RESET
START
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
.
Keypad
Monitor Mode
LEDs
Display
Drive Status LEDs
Start Key
Stop / Reset
Key
Password LED
¥
Jumpers
JP1
(for U-phase)
JP2
(for V-phase)
JP3
(for bus current)
JP4
(for bus current)
JP6
Description
These jumpers are used for selection of
current feedback gain as follows:
A:
for 30 to 50 HP units
B:
for 60 to 100 HP units
This jumper is used for selection of ON/OFF
level of precharge relay as follows:
A: ON at 175 V, OFF at 155 V
B: ON at 220 V, OFF at 200 V
Factory Setting
For 30 to 50 HP units:
:
A
For 60 to 100 HP
units: B
Set to A position