Wiring the Regulator Board Terminal Strip

Parameters/Wiring Connections

The following parameters must be set:

P.026: Function Loss Response

A signal must be present at terminal 20 for the drive to be able to
start. See figures 7.1 and 7.2 The drive is shipped from the factory
with a jumper between terminals 16 and 20 which provides the
signal. The function loss input should be in series with the drive's
external interlocks. In this case, the jumper must be removed
before the connections are made. See figure 2.7.

Terminal 20 On = No Function Loss

The following parameters must be set:

P.000: Control Source
P.020: Jog Speed Reference
P.021: Jog Ramp Accel Time
P.022: Jog Ramp Decel Time

Terminal 21 On = Jog Operation

Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)

Terminal

Number

20

21

Description

Digital Input 5
(Function Loss)

Digital Input 4
(Run/Jog)

Wiring a Function Loss Input

16 17 18 19 20 21

16 17 18 19 20 21

REMOVE FACTORY FUNCTION
LOSS JUMPER HERE.

FUNCTION LOSS
COAST-STOP
PUSH-BUTTON

SAFETY INTERLOCKS

TERMINAL STRIP

16

21

RUN

JOG

Wiring a Run/Jog Input