beautypg.com

Rockwell Automation GV3000/SE AC Drive 30-100HP, 230VAC V6.04 Hardware Ref, Install, Troubleshooting User Manual

Page 35

background image

3-7

Planning Before Installing

GV3000/SE

HP Rating

Filter Type

Maximum Lead Length in Feet with

230 VAC Motor

Carrier Frequency

30
40
50
60
75

100

30
40
50
60
75

100

None

A 5%MTE

reactor/filter
at the drive.

2 kHZ

800
800
800
800
800
800

1000
1000
1000
1000
1000
1000

4 kHZ

500
500
500
500
500
500

1000
1000
1000
1000
1000
1000

8 kHZ

500
500
500
500
500
500

1000
1000
1000
1000
1000
1000

Table 3.6 - Motor Lead Lengths

Table 3.7 - Reactors

Note that the lead lengths listed are valid with Reliance Electric inverter duty motors.

GV3000/SE

HP Rating

30
40
50

240 Volt

5% MTE Reactor

RL-08002
RL-10002
RL-13002

GV3000/SE

HP Rating

60
75

100

240 Volt

5% Reactor

RL-16002
RL-20002
RL-25002

GV3000/SE

Drive

GV3000/SE

Drive

GV3000/SE

Drive

GV3000/SE

Drive

Motor

Motor

Motor

Motor

Motor

Motor

Motor

38 m (125')

38 m (125')

15 m (50')

61 m (200')

8 m (25')

61 m (200')

8 m (25')

76 m (250')

All examples represent 76 m (250') of motor lead length.

Figure 3.3 - How to Measure Motor Lead Lengths

These part numbers are for a reactor with a cacitor filter.
MTE standard reactors can be used on GV3000/SE drives with carrier frequency settings up to 8 kHZ.
All reactors are UL-recognized (UL-506 File #E53094) and CSA certified (CSA File #LR29753).