beautypg.com

3 wiring the signal and control i/o – Rockwell Automation GV3000/SE AC Drive 30-100HP, 230VAC V6.04 Hardware Ref, Install, Troubleshooting User Manual

Page 59

background image

7-9

Wiring the Regulator Board Terminal Strip

Parameters/Wiring Connections

Note that RS-232 communication between the GV3000/SE drive
and a personal computer requires the use of the Control and
Configuration software. Refer to instruction manual D2-3348 for
more information.

These terminals should only be used when the RS-232 port
(J8) or an Operator Interface Module (OIM) are not being used, as
all three devices use the same transmit/receive lines.

See section 7.2.

Description

RS-232 Transmit

RS-232 Receive

RS-232 Signal/Regulator
Common

Encoder Wiring

Wiring RS-232 Signals

Terminal

Number

1

2

3

4-9

Wiring Encoder Inputs

1 2 3

TERMINAL STRIP

PERSONAL COMPUTER

25 PIN D–SHELL, MALE –OR–
9 PIN D–SHELL, PLUG

TXD [DATA OUT] TERMINAL 1

RXD [DATA IN] TERMINAL 2

COMMON TERMINAL 3

–OR–

1

1

PIN–2 RXD [DATA IN]

PIN–3 TXD [DATA OUT]

COMMON

PIN–7 (25– PIN D–SHELL)

–OR–

PIN–5 (9–PIN D–SHELL)

WIRE LENGTH – 50 FEET [MAX]

7.3 Wiring the Signal and Control I/O

Wire the drive's signal and control I/O to the terminal strip as shown in table 7.8.

Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip