Xm services – Rockwell Automation 1440-TTC06-00RE XM-362 Temperature Module User Manual
Page 81
Publication GMSI10-UM008D-EN-P - August 2010
73
XM Services
The table below defines the services supported by the XM modules. The table
includes the service codes, classes, instances, and attributes by their
appropriate hexadecimal codes. Use the Class Instance Editor in RSNetWorx
to execute these services, as illustrated in the following example.
XM Services
Action
Service Code
(Hex)
Class
(Hex)
Instance
Attribute
Data
Transition to Run Mode
Start
(06)
Device Mode Object
(320)
1
None
None
Transition to Program Mode
Stop
(07)
Device Mode Object
(320)
1
None
None
Save configuration to
non-volatile memory (EEPROM)
Save
(16)
Device Mode Object
(320)
1
None
None
Delete saved configuration from
non-volatile memory (EEPROM)
Delete
(09)
Device Mode Object
(320)
1
None
None
Reset a specific latched relay
Reset
(05)
Relay Object
(323)
Relay number
1-C for XM-440,
1-5 for XM-12X,
XM-320 and
XM-220, 1-8 for
XM-36X and
XM-16X
None
None
Reset all latched relays
Reset
(05)
Relay Object
(323)
0
None
None
Reset the Peak Speed (XM-12X
only)
Reset
(05)
Speed Measurement
Object
(325)
1, 2 for XM-220
None
None
Close the virtual setpoint
multiplier switch to activate the
alarm setpoint multipliers (not
applicable to all XM modules)
Other
(33)
Discrete Input Point
Object
(08)
1
None
None
Open the virtual setpoint
multiplier switch to start the
setpoint multiplier timers and
eventually cancel alarm setpoint
multiplication (not applicable to
all XM modules)
Other
(32)
Discrete Input Point
Object
(08)
1
None
None