103
Alarm Object
(Class ID 31D
H
)
The Alarm Object models a two-stage (alert and danger levels) alarm.
Class Attributes
The Alarm Object provides no class attributes.
Instances
There are 18 instances of this object. Instances 1-6 are associated with the 6
AIP Object measurement values. Instances 7-12 are associated with the 6 AIP
Object rate values. And instances 13-18 are associated with the 6 Parameter
Object difference calculations.
Instance Attributes
Table C.31 Alarm Object Instance Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics
3
Get
Alarm Status
3 BITS
The current status of the
alarm.
0 = Normal
1 = Alert (alarm)
2 = Danger (shutdown)
3 = Disarm
4 = Sensor Out of Range (OOR)
Fault
5 = Module Fault
4
Get/Set
Alarm Enable
BOOL
Indicates whether this
alarm object is enabled.
0 = Disabled
1 = Enabled
6
Get
Threshold Units
USINT
Indicates whether the
threshold and hysteresis
value are specified in
units of measure.
Set to 1
1 = Measurement units
7
Get/Set
Condition
USINT
Indicates on which side of
the threshold values the
alarm and danger
conditions exist.
0 = Greater than
1 = Less than
2 = Inside range
3 = Outside range
8
Get/Set
Alert Threshold
(High)
REAL
The threshold value for
the alert (alarm) condition
(greater threshold for
range types).
9
Get/Set
Danger Threshold
(High)
REAL
The threshold value for
the danger (shutdown)
condition (greater
threshold for range types).