A special cable (Cat. No. 1440-SCDB9FXM2) is required for this serial
connection. The connector that inserts into the PC is a DB-9 female
connector, and the connector that inserts into the module is a USB Mini-B
male connector.

DeviceNet Connection

The XM-361 and XM-362 include a DeviceNet™ connection that allows the
modules to communicate directly with a programmable controller, DCS, or
another XM module.

DeviceNet is an open, global, industry-standard communications network
designed to provide an interface through a single cable from a programmable
controller to a smart device such as the XM-361 or XM-362. As multiple XM
modules are interconnected, DeviceNet also serves as the communication bus
and protocol that efficiently transfers data between the XM modules.

Connect the DeviceNet cable to the terminal base unit as shown.

WARNING

If you connect or disconnect the serial cable with power
applied to the module or the serial device on the other end
of the cable, an electrical arc can occur. This could cause an
explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before
proceeding.

IMPORTANT

If 24V Common is not referenced to earth ground, we
recommend you use an RS-232 isolator, such as Phoenix
PSM-ME-RS232/RS232-P (Cat. No. 1440-ISO-232-24), to
protect both the XM module and the computer.

Connect

To

Terminal Base Unit

Red Wire

DNet V+

47 (Optional - see note)

White Wire

CAN High

44

Bare Wire

Shield (Chassis)

46

Blue Wire

CAN Low

45

Black Wire

DNet V-

48