Class attributes, Instances, Instance attributes – Rockwell Automation 1440-TTC06-00RE XM-362 Temperature Module User Manual
Page 109: Services, Instance attributes services

Publication GMSI10-UM008D-EN-P - August 2010
101
Class Attributes
The Analog Input Group Object provides no class attributes.
Instances
There is one Analog Input Group Object instance that models the shared
parameters for the set of all Analog Input Point instances.
Instance Attributes
Services
1
Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
Table C.27 Analog Input Group Object Instance Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics
8
Get
Value Data Type USINT
Determines the data type
of the AIP value.
1 = REAL
10
Get/Set
Temp Mode
BOOL
Temperature scale to use
when reporting a value.
0 = Celsius
1 = Fahrenheit
103 Get
Cold
Junction
Temperature
REAL
Temperature of
TC-terminal block
junction.
105
Get
Cold Junction
Underrange
BOOL
Indicates cold junction
measurement is invalid on
the low side.
106
Get
Cold Junction
Overrange
BOOL
Indicates cold junction
measurement is invalid on
the high side.
Table C.28 Analog Input Group Object Services
Service
Code
Class/Instance Usage
Name
Description
0E
h
Instance
Get_Attribute_Single Returns the contents of the
specified attribute.
10
h
Instance
Set_Attribute_Single
Sets the contents of the
specified attribute.
1