Rockwell Automation 1440-TTC06-00RE XM-362 Temperature Module User Manual
Page 63
Publication GMSI10-UM008D-EN-P - August 2010
55
Sets the alarm conditions that will cause the relay to
activate. You can select more than one.
• Normal - The current measurement is not within
excess of any alarm thresholds.
• Alert - The current measurement is in excess of
the alert level threshold(s) but not in excess of the
danger level threshold(s).
• Danger - The current measurement is in excess of
the danger level threshold(s).
• Disarm-The alarm is disabled or the device is in
Program mode.
• Sensor OOR - The signal from the sensor is
outside the Sensor Range.
• Module Fault - Hardware or firmware failure, or
an error has been detected and is preventing
proper operation of the device.
Options: Normal
Danger
Sensor OOR
Alert
Disarm
Module Fault
Check to enable.
Clear to disable.
Relay Installed
Indicates whether the relay is a physical relay on a
module or a virtual relay. If the relay is a physical
relay, then you can set the Failsafe parameter.
If the relay is a virtual relay, the Failsafe parameter
is not used or it is disabled.
Relay Parameters
Parameter Name
Description
Options/Comments
XM Configuration
Utility
EDS File
Alarm Status to
Activate On
Alarm Levels
XM Configuration
Utility
EDS File
Check = Physical
Relay
Installed =
Physical Relay
Clear = Virtual Relay Not Installed =
Virtual Relay