Publication GMSI10-UM008D-EN-P - August 2010
19
5
RTD 2 (+)
No Connection
Constant current is sourced to the RTD
Positive voltage across the RTD is measured here
Redundant terminal should remain unterminated
6
RTD 2 (+
No Connection
7
RTD 3 (+)
No Connection
Constant current is sourced to the RTD
Positive voltage across the RTD is measured here
Redundant terminal should remain unterminated
8
RTD 3 (+)
No Connection
9
RTD 4 (+)
No Connection
Constant current is sourced to the RTD
Positive voltage across the RTD is measured here
Redundant terminal should remain unterminated
10
RTD 4 (+)
No Connection
11
RTD 5 (+)
No Connection
Constant current is sourced to the RTD
Positive voltage across the RTD is measured here
Redundant terminal should remain unterminated
12
RTD 5 (+)
No Connection
13
RTD 6 (+)
No Connection
Constant current is sourced to the RTD
Positive voltage across the RTD is measured here
Redundant terminal should remain unterminated
14
RTD 6 (+)
No Connection
15
Chassis
Connection to DIN rail ground spring or panel mounting hole
16
4-20 mA 1 (+)
4-20 mA output 1, positive side
17
4-20 mA 2 (+)
4-20 mA output 2, positive side
18
4-20 mA 3 (+)
4-20 mA output 3, positive side
19
TC 1 (+) / RTD 1 (-)
TC 1 (+)
Positive terminal when channel configured as a
thermocouple input
Negative side of the voltage across the RTD in an RTD
configuration
Positive side of the lead wire detection in a 3-wire RTD
configuration
20
TC 1 (-) / RTD 1 (-)
TC 1 (-)
Negative terminal when channel configured as a
thermocouple input
Constant current return in an RTD configuration
Negative side of the lead wire detection
21
TC 2 (+) / RTD 2 (-)
TC 2 (+)
Positive terminal when channel configured as a
thermocouple input
Negative side of the voltage across the RTD in an RTD
configuration
Positive side of the lead wire detection in a 3-wire RTD
configuration
22
TC 2 (-) / RTD 2 (-)
TC 2 (-)
Negative terminal when channel configured as a
thermocouple input
Constant current return in an RTD configuration
Negative side of the lead wire detection
23
TC 3 (+) / RTD 3 (-)
TC 3 (+)
Positive terminal when channel configured as a
thermocouple input
Negative side of the voltage across the RTD in an RTD
configuration
Positive side of the lead wire detection in a 3-wire RTD
configuration
Terminal Block Assignments
Name
No.
XM-361
XM-362
Description