Rockwell Automation 1440-TTC06-00RE XM-362 Temperature Module User Manual
Page 75
Publication GMSI10-UM008D-EN-P - August 2010
67
RTD Current Source Value
Isolation
(XM-362 only)
Common Mode Input Voltage
(XM-361 only)
Input Impedance
1.004 mA ±1%
Up to 250 volts of isolation for each input
±3 Volts
XM-361: 1 Mohm voltage input
XM-362: 10 k voltage input
Outputs
4-20 mA Outputs
Accuracy
Isolation
Two isolated banks of three outputs (one
per channel)
600 ohm max load
±1% of full scale max
±0.2% of full scale typical
250 Volts
Indicators
6 LEDs Module Status - red/green
Network Status - red/green
Channel 1 Status - yellow/red
Channel 2 Status - yellow/red
Channel 3 Status - yellow/red
Channel 4 Status - yellow/red
Channel 5 Status - yellow/red
Channel 6 Status - yellow/red
Signal Conditioning
Accuracy
Resolution
Low Pass Filter
Sampling Rate
Measured Units
C Thermocouples: ±3°C (±6°F) or 0.6% of
full scale, whichever is greater
E, J, K, N, T Thermocouples: ±1°C (±2°F) or
0.6% of full scale, whichever is greater
B, R, S Thermocouples: ±4°C (±7°F) or 0.6%
of full scale, whichever is greater
Platinum & Nickel RTDs (3-wire only): ±1°C
(±2°F) or 0.6% of full scale, whichever is
greater
Copper RTDs (3-wire only): ±7°C (±13°F) or
5% of full scale, whichever is greater
RTDs and Thermocouples: 0.025% of
temperature range
User configurable for the measurement and
rate of change value from each channel
200 Hz
°F
°C
XM-361/362 Technical Specifications
Product Feature
Specification