WebPak 3000 OIM User Guide
POSITIVE
CURRENT
LIM
(P.005)
Sets the highest
amount of current (%
full load amps) for the
forward bridge.
Parameter Range:
0 to
MAXIMUM
CURRENT
(%
FLA
)
Default Setting:
150 %
FLA
Parameter Type:
Tunable
This parameter is used as a high limit for the speed loop
PI
block when
POS
CURRENT
LIM
SEL
(P.223) is set to
REGISTER
.
NEGATIVE
CURRENT
LIM
(P.006)
Selects the highest
amount of current (%
full load amps) for the
reverse bridge.
Parameter Range:
When
NEG
CUR
LIM
INV
EN
(P.226) =
ENABLED
:
0 to
MAXIMUM
CURRENT
(%
FLA
)
When
NEG
CUR
LIM
INV
EN
(P.226) =
DISABLED
:
–
MAXIMUM
CURRENT
to 0 (%
FLA
)
Default Setting:
±150 %
FLA
Parameter Type:
Tunable
This parameter is used as a low limit for the speed loop
PI
block when
NEG
CURRENT
LIM
SEL
(P.224) is set to
REGISTER
.
The range of
NEGATIVE
CURRENT
LIM
depends on the setting of
NEG
CUR
LIM
INV
EN
(P.226).
IR
COMPENSATION
(P.206)
Sets the armature
voltage loss
compensation value
used when the drive
is configured as a
voltage regulator.
Parameter Range:
0 to 50%
Default Setting:
0%
Parameter Type:
Tunable
This parameter is also used by the Field Current Regulator kit to set the
field-weakened threshold.
IR
COMPENSATION
is normally determined from the motor data sheet. It should be
set to the percent
IR
drop of the motor.
If this data is not available on the motor data sheet, you can set this empirically so
that the no-load and full-load speeds are as close as possible when operating as a
voltage regulator.
This parameter is not available for current/torque regulated drives.
!
ATTENTION: The incorrect configuration of
IR
COMPENSATION
(P.206)
can cause an overspeed condition. This parameter must be configured
by a qualified person who understands the significance of configuring it
accurately. Failure to observe this precaution could result in bodily injury.