Using Quick Start
5-13
MAXIMUM
SPEED
(P.004)
The maximum speed
of the drive that can
be supported by the
application or
process.
Parameter Range:
1 to
GEAR
IN
SPEED
(P.011) (
RPM
or user-defined
units)
Default Setting:
500
RPM
Parameter Type:
Tunable
If raising this value causes
MINIMUM
SPEED
(P.003) to become less than 10% of
MAXIMUM
SPEED
, an alarm is generated.
This is typically set to base speed from the motor nameplate.
!
ATTENTION:
MAXIMUM
SPEED
is a tunable parameter and could affect
speed it if is adjusted while the drive is running. Failure to observe this
precaution could result in severe bodily injury or loss of life.
ATTENTION: Do not allow the motor to exceed the maximum safe speed,
as determined by the equipment manufacturer, of the motor or the driven
equipment. Failure to observe this precaution could result in bodily injury.
JOG
ACCEL
/
DECEL
TIME
(P.013)
Sets the minimum
time that the jog
reference can change
from zero to
GEAR
IN
SPEED
(P.011) and
from
GEAR
IN
SPEED
to zero.
Parameter Range:
0.1 to 300.0
SECONDS
Default Setting:
3.0
SECONDS
Parameter Type:
Tunable
The
S
-
CURVE
ROUNDING
(P.014) parameter does not affect the setting of this
parameter.
JOG
SPEED
(P.012)
Specifies the speed
level for jogging in
either the forward or
reverse direction.
Parameter Range:
0 to
BASE
SPEED
(P.017)
Default Setting:
250
FPM
Parameter Type:
Tunable
!
ATTENTION: This drive can operate at and maintain zero speed when
JOG
SPEED
(P.012) is set to zero. A voltage-regulated drive can produce
zero speed at low minimum speed values. The user is responsible for
assuring safe conditions for operating personnel by providing suitable
guards, audible or visual alarms, or other devices to indicate that the
drive is operating at or near zero speed. Failure to observe this precaution
could result in severe bodily injury or loss of life.