Rockwell Automation WebPak 3000 User Guide User Manual
Page 39
Using Quick Start
5-3
Step 5. Use the procedure described in section 4.2.5 to change the value.
Press
. Quick Start automatically takes you to the next parameter
entry screen.
Step 6. Continue going through the Quick Start parameters, changing values as
needed. Press
to accept values and move to the next parameter.
Step 7. After the final parameter entry screen (
MOTOR
HOT
FLD
AMPS
(P.510)), the
Correct Scaling Jumper Positions screen is displayed. This shows the
correct settings for three of the jumpers on the Regulator board. See the
hardware manual for information on setting the jumpers. Press
after
checking the jumpers.
Step 8. The Quick Start Complete screen is displayed, as shown in figure 5.3.
Step 9. You can either start self-tuning or exit Quick Start.
•
To start self-tuning: Select
YES
. See section 5.4, “Self-Tuning the Current
Minor and Speed Loops”, for information on self-tuning. When self-tuning
is complete, you are returned to the Main Menu.
•
To exit Quick Start without self-tuning: Select
NO
. The Main Menu is
displayed.
Step 10. To save the changes made to parameters during Quick Start, you must do a
Memory Save. See section 4.4, “Saving and Restoring Parameter Values”.
Figure 5.2 – First Quick Start Parameter Entry Screen
!
ATTENTION: The drive will not operate at the correct speed if hardware
jumpers J11, J14, and J18 are not set as indicated on the
OIM
during
Quick Start. Failure to observe this precaution could result in damage
to, or destruction of, the equipment.
Figure 5.3 – Quick Start Complete Screen