beautypg.com

Rockwell Automation FactoryTalk View Site Edition Installation Guide User Manual

Page 128

background image

F

ACTORY

T

ALK

V

IEW

I

NSTALLATION

G

UIDE

114

• •

5. In this upgrade example, because System information was included when the

application was backed up (see “Back up the application” on page 107), Application
and System
should be displayed in the field, Archive type.

Select the check box, Restore System, and then click OK.

Disable redundancy and make Server #2 the primary server

1. On Server #2, open the restored application in FactoryTalk View Studio.

To open the Administration Console, click Start > All Programs > Rockwell
Software > FactoryTalk View > FactoryTalk View Studio
.

2. After the application opens, right-click the HMI server, and then click Properties.

3. In the Redundancy tab, clear the check box, Provide redundancy using a

secondary server, and then click Apply.

4. In the General tab, in the field, Computer hosting the server, type Server #2, and then

click OK.

Restoring System information replaces user and computer accounts as well as RSLinx
Enterprise device paths which were set up in the FactoryTalk Directory on the local computer.

FTViewSEInstallENU.book Page 114 Wednesday, July 16, 2014 10:53 AM