English – Rockwell Automation SP120 ACDrive 115VAC, 1Ph, 230VAC, 1Ph/3Ph, 1/4-5.0HP User Manual
Page 43
Parameters and Programming
3-13
English
Parameter
Number
Parameter Name/ Description
Min./Max
Range
Units
Factory
Default
DC Brake
A51
DC Brake Enable
Used to enable/disable DC injection braking
Settings: 00=Disabled
01=Enabled
00 to 01
Numeric
Value
00
A52
DC Brake Start Frequency
Sets the frequency at which the DC brake will become
active.
0.5 to 10.0
0.1 Hz
10.0
A53
DC Brake Wait Time
Sets the time the drive will wait after A52 [
DC
BRAKE
START
FREQUENCY
] before applying A54 [
DC
HOLD
VOLTAGE
].
0.0 to 5.0
0.1 sec
0.0
A54
DC Hold Voltage
Sets the level of DC braking voltage in percent of A82
[
BASE
VOLTAGE
].
0 to 100
1% of drive
rating
0
A55
DC Hold Time
The time that A54 [
DC
HOLD
VOLTAGE
] is applied to the
motor after A53 [
DC
BRAKE
WAITING
TIME
] has expired.
0.0 to 60.0
0.1 sec
0.0
Operating Frequency Range
A61
Upper Frequency Limit
This is an upper frequency limit similar to A04 [
MAXIMUM
FREQUENCY
] except that it can be set lower than A03
[
BASE
FREQUENCY
]. A value of 0.0 will disable this
parameter.
Output Frequency
0.5 to 360.0
0.1Hz
0.0
A62
Minimum Frequency
Lowest frequency the drive will output continuously.
Refer to diagram in A61 [
UPPER
FREQUENCY
LIMIT
].
0.0 to 360.0
0.1Hz
0.0
A63
Skip Frequency 1
Sets a frequency at which the drive will not output
continuously.
0.0 to 360.0
0.1Hz
0.0
A64
Skip Frequency Band 1
Sets the bandwidth around A63 [
SKIP
FREQUENCY
1].
The bandwidth is 2x A64 [
SKIP
FREQUENCY
BAND
1] with
½ the band below and ½ the band above A63 [
SKIP
FREQUENCY
1].
0.0 to 10.0
0.1Hz
0.5
A65
Skip Frequency 2
Sets a frequency at which the drive will not output
continuously.
0.0 to 360.0
0.1Hz
0.0
A61
Frequency Command
A62