Installing and Wiring the Drive
2-13
English
11
{FRS}
Coast to Stop
The motor voltage will be switched off immediately and the motor will
coast. This function can be programmed to operate in two different
modes via parameter b88 [FRS Select].
Note: The drive will start when 11 {FRS} input is removed without
reissuing a start command even if in 3-wire (momentary) control.
12
{EXT}
External Fault
When this input is active, an E12 fault indication will be issued (e.g. an
input received from thermal contacts). The fault indication will be
cleared with a reset 18 {RS}.
Important: After a reset 18{RS} command, the drive will start again if a
start command is active (00{FW}, 01{RV},or 20 {STA}).
13
{USP}
Unintentional
Start Protection
on Power Up
This function is designed to guard against unintended starting when
input power is removed and then restored. In this case, if a start/run
command is issued immediately upon/after power is restored an E13
fault will be issued. A new start command or a reset 18 {RS} command
will clear the fault indication.
15
{SFT}
Program Lock
Protects stored parameter values from being overwritten. See
parameter b31 [
PROGRAM
LOCK
SELECT
] for the 4 different levels of
protection.
Table 2.5 – Programmable Digital Input Functions
Numeric
Setting
Alpha
Setting
Function
Description
synchronization of
motor speed
0 Hz start
Run (NO)
Input 11 {FRS} (NO)
Motor Speed
Waiting time
Run (NO)
Input 12 {EXT} (NO)
Motor Speed
Input 18 {RS} (NO)
Fault relay (AL0-Al2) (NO)
Motor will
Coast
Power Supply
00{FW} or
01 {RV} (N.O.)
13 {USP}(N.C.)
Fault relay (N.O.)
Motor Speed
Min. 3 Sec