Rockwell Automation Publication 2711P-UM006C-EN-P - April 2013

37

Install Terminal

Chapter 2

Remove and Install the
Power Terminal Block

The terminals are shipped with a power terminal block installed. You can remove
the terminal block for ease of installation, wiring, and maintenance.

The terminal blocks have different colors and markings for AC and DC power
connections. Always match the terminal block color to its mating connector. The
power terminal blocks are not intended for daisy chaining power.

Use a 0.6 x 3.5 mm flat blade screwdriver for terminal block wiring.

400 and 600 Terminals

Follow these steps to remove the terminal block from a 400 or 600 terminal.

1. Insert the tip of a small, flat-blade screwdriver into the terminal block

access slot.

2. Gently pry the terminal block to rotate it away from the terminal; this

releases the locking mechanism.

Follow these steps to replace the terminal block.

1. Press terminal block base in first with block leaning outward.

2. Gently push the top of the terminal block to rotate it into place; it snaps

when seated.

WARNING: Explosion Hazard
If you connect or disconnect wiring while the power is on, an electrical arc can
occur. This could cause an explosion in hazardous location installations. Be sure
that power is removed and the area is nonhazardous before proceeding.

Failure to remove power can result in electrical shock or damage to the terminal.

Table 36 - Wire Specifications for Power Input Terminal Block

Terminal

Wire Type

Dual-wire Size

(1)

(1) Two-wire max per terminal.

Single-wire Size

Strip Length

Screw Torque

400, 600

Stranded or solid
Cu 90 °C (194 °F)

0.3…1.3 mm

2

22…16 AWG

0.3…2.1 mm

2

(22…14 AWG)

7 mm (0.28 in.)

0.45…0.56 N•m
(4…5 lb•in)

700 to 1500

0.56 …0.90 N•m
(5…8 lb•in)