Chapter 2
Installation
2-13
82
W
resistor
Clear
Shield
Blue
Use the 3-pin connector on the processor to connect a DH+ link.
The connector’s port must be configured to support a DH+
communication link.
You can connect a DH+ link two ways:
•
trunkline/dropline—from the dropline to the connector screw
terminals on the DH+ connectors of the processor
•
daisychain—to the connector screw terminals on the DH+
connectors of the processor
To make connections:
1. Connect the signal conductor with CLEAR insulation to the
3-pin connector terminal 1 at each end of each cable segment.
2. Connect the SHIELD drain wire to the 3-pin connector SH
terminal at both ends of each cable segment.
3. Connect the signal conductor with BLUE insulation to the 3-pin
connector terminal 2 at each end of each cable segment.
For more information, see the Data Highway/Data Highway
Plus/Data Highway II/Data Highway 485 Cable Installation Manual,
publication 1770-6.2.2.
Chan 0
Chan 2
To connect a programming terminal via the 8-pin
connector on a PLC-5/VME processor on a DH+
link, use the following:
Communication card
to access a DH+ link
Cable
1784-PCMK
1784-PCM5 with a
1784-CP7 adapter
1784-KTX
1784-CP12 with a
1784-CP7 adapter
OR
1784-CP13 direct
connect to the front
of the PLC-5/VME
processor
8-pin
Mini-DIN
8-pin
Mini-DIN
PLC-5/V40B or -5/V80B
PLC-5/V40L
Programming Terminal
1784-CP6
1784-CP6