beautypg.com

Rockwell Automation 1785-Vx0B, D17856.5.9 PLC-5 VME VMEbus Programmable Controllers User Manual User Manual

Page 118

background image

Performance and Theory of Operations

Chapter 7

7-13

Extended-Local I/O

Processors that have extended-local I/O capability scan the extended-local
I/O chassis (on channel 2) during the housekeeping portion of the program
scan. Extended-local I/O discrete data is exchanged between the processor
data-table image and the I/O in the extended-local I/O chassis. The time
that it takes to scan extended-local I/O chassis is added to the
housekeeping time. See Figure 7.2.

Figure 7.2
Extended-Local I/O Scan Time

Processor
Checks

Remote
I/O Buffer

Extended-

Update

Local I/O
Scan

Housekeeping

Logic Scan

Program Scan

+

The time in ms that it takes to scan extended-local I/O chassis depends on
the number of 1771-ALX adapter modules and the number of extended-
local I/O logical racks. The formula used to calculate the total time to scan
extended-local I/O chassis is:

extended-local

I/O

scan

time

=

(0.32

ms

x

A)

+

(0.13

ms

x

L)

Where:

Is the:

A

number of 1771-ALX modules

L

number of logical racks in the extended-local I/O system

If you have three 1771-ALX modules in three chassis and a total of 4
logical racks, for example, the total time is calculated as follows:

extended-local

I/O

scan

time

=

(0.32

ms

x

3)

+

(0.13 ms

x

4)

or

extended-local

I/O

scan

time

=

1.48

ms

housekeeping

time

=

1.48

ms

(extended-local

I/O)

+

4.50

ms

(other housekeeping) or

housekeeping time

=

5.98

ms