Appendix D
Troubleshooting
D-4
The codes returned in the EXT STS (extended status) field when the
remote error (STS) is F0H are listed below:
Code (hex)
Explanation
0
Not used
1
A field has an illegal value
2
Less levels specified in address than minimum for any address
3
More levels specified in address than system supports
4
Symbol not found
5
Symbol is of improper format
6
Address does not point to something usable
7
File is wrong size
8
Cannot complete request, situation has changed since start of command
9
Data or file is too large
A
Transaction size plus word address is too large
B
Access denied, improper privilege
C
Condition cannot be generated—resource is not available
D
Condition already exists—resource is already available
E
Command cannot be executed
F
Histogram overflow
10
No access
11
Illegal data type
12
Invalid parameter or invalid data
13
Address reference exists to deleted area
14
Command execution failure for unknown reason
15
Data conversion error
16
Scanner not able to communicate with 1771 rack adapter
17
Adapter cannot communicate with module
18
1771 module response was not valid
19
Duplicated label
1A
File is open; another node owns it
1B
Another node is the program owner
1C TO FF
Not used
If you receive a code other than the above, you are using a PCCC not
described in this manual and should consult the documentation you are
using to understand that PCCC and its specific error codes.