Chapter 5

5-8

Figure 5.6

Illustration of 2ĆSlot Addressing with 16ĆPoint Input and Output Modules

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

00

01

02

03

04

05

06

07

10

11

12

13

14

15

16

17

17 16 15 14

12

10 07 06 05

03 02 01 00

04

11

13

17 16 15 14

12

10 07 06 05

03 02 01 00

04

11

13

11869

16Ćpoint input and output modules use

two words (one input, one output) of the

image table.

Output image table word corresponding

to the I/O group (all bits used)

Input image table word corresponding

to the I/O group (all bits used)

input

terminals

2Ćslot

I/O group

output

terminals

Because these modules use a full word in the image table, the only type of
module you can use in a 2-slot I/O group with a 16-point module is one
that performs the opposite (complementary) function; an input module
complements an output module and vice-versa.

You can use an 8-point module with a 16-point module in a 2-slot group;
however, it too must perform the opposite function. Eight bits in the I/O
image table are unused.

Important: 32-point modules will not work in 2-slot addressing mode.