Module tags for 1732e-ir4im12r – Rockwell Automation 1732E-IR4IM12R ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD User Manual
Page 77

Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
69
Module Tag Definitions Appendix C
Module Tags for 1732E-IR4IM12R
C.Ch0HAlarmLimit
C.Ch1HAlarmLimit
C.Ch2HAlarmLimit
C.Ch3HAlarmLimit
INT
The high alarm trigger point. This value causes the Ch<0...3>HAlarm bit to trigger when the input signal
moves above the configured trigger point, in engineering units.
C.Ch0LLAlarmLimit
C.Ch1LLAlarmLimit
C.Ch2LLAlarmLimit
C.Ch3LLAlarmLimit
INT
The low low alarm trigger point. This value causes the Ch<0...3>LLAlarm bit to trigger when the input
signal moves beneath the configured trigger point, in engineering units.
C.Ch0HHAlarmLimit
C.Ch0HHAlarmLimit
C.Ch0HHAlarmLimit
C.Ch0HHAlarmLimit
INT
The high high alarm trigger point. This value causes the Ch<0...3>HHAlarm bit to trigger when the input
signal moves above the configured trigger point, in engineering units.
Ch0TempMode
Ch1TempMode
Ch2TempMode
Ch3TempMode
SINT
Controls the temperature scale to use on the module.
0 = Celsius
1 = Fahrenheit
Ch0CJEn
Ch0CJEn
Ch0CJEn
Ch0CJEn
SINT
Enables the cold junction sensor that turns on cold junction compensation to linearize thermocouple
inputs.
Ch0CJOffset
Ch1CJOffset
Ch2CJOffset
Ch3CJOffset
INT
Provides a user-defined offset to add into the read cold-junction sensor value. Allows a sensor with a
built-in bias to be compensated for.
Configuration Tags (1732E-IT4IM12R)
Tag Name
Data Type
Definition
Input Tags (1732E-IR4IM12R)
Tag Name
Data Type
Definition
I.Fault
DINT
Collection of all module level fault bits
I.Ch0Data
I.Ch1Data
I.Ch2Data
I.Ch3Data
INT
The channel input signal represented in counts where -32,768 counts is the minimum detectable input
signal and 32,767 counts is the maximum detectable.
I.Ch0Fault
I.Ch1Fault
I.Ch2Fault
I.Ch3Fault
BOOL
Individual channel fault status bit. Indicates a ‘hard’ fault has occurred on the channel that means:
calibration is ongoing; or if an input, an overrange or underrange condition is present. These bits also
are set by the controller if communication is lost with the I/O module.
I.Ch0Calibration
I.Ch1Calibration
I.Ch2Calibration
I.Ch3Calibration
BOOL
Indicates if calibration is currently in progress on a channel.
I.Ch0LAlarm
I.Ch1LAlarm
I.Ch2LAlarm
I.Ch3LAlarm
BOOL
Low alarm bits that set when the input signal moves beneath the configured low alarm trigger point,
Ch<0...3>LAlarmLimit. Remains set until the input signal moves above the trigger point, unless latched
via Ch<0...3>LimitAlarmLatch, of the low alarm trigger point.
I.Ch0HAlarm
I.Ch1HAlarm
I.Ch2HAlarm
I.Ch3HAlarm
BOOL
High alarm bit that sets when the input signal moves above the configured high alarm trigger point,
Ch<0...3>HAlarmLimit. Remains set until the input signal moves below the trigger point, unless latched
via Ch<0...3>LimitAlarmLatch.
I.Ch0LLAlarm
I.Ch1LLAlarm
I.Ch2LLAlarm
I.Ch3LLAlarm
BOOL
Low low alarm bit that sets when the input signal moves beneath the configured low low alarm trigger
point, Ch<0...3>LLAlarmLimit. Remains set until the input signal moves above the trigger point, unless
latched via Ch<0...3>LimitAlarmLatch.