Download the program to your controller – Rockwell Automation 1732E-IR4IM12R ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD User Manual
Page 28
20
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Chapter 3 Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software
Note that we have used the following properties in this example:
To add the 1732E-IR4IM12R RTD module, follow the same steps. After
adding the modules to your project, the I/O Configuration tree should
appear as follows:
This example uses default Module Definition and configuration
properties. To edit your configuration, see
Download the Program to
Your Controller
After you write configuration for your module, the module does not use this
configuration until you download it to the owner-controller. The download
transfers the entire program to the controller, overwriting any existing program.
Download module configuration as shown below:
Depending on your application, a variety of RSLogix 5000 software screens may
appear to choose a path to your ControlLogix controller and to verify the
download. Navigate those screens as best fits your application.
This completes the download process.
Field Name
Value
Name
TEST_1732EIT4IM12R
IP address
192.168.1.3
Electronic keying
Compatible Module
Revision
1.1
Connection
Input Only
A. Click here to see the
pull-down menu.
B. Click download.