Rockwell Automation 1732E-IR4IM12R ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD User Manual
Page 66

58
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Appendix A Specifications
The 1732E-IR4IM12R RTD input module has the following input
specifications.
Thermocouple types
Type
Material
Temperature
Range °C (°F)
Voltage
Range (mV)
B
Pt /30% Rh vs. Pt/
5% Rh
40…1820
(104…3308)
0…13.820
C
W/5% Re vs. W/
26% Re
0…2320
(32…4208)
0…37.107
E
Ni/Cr vs. Cu/Ni
-270…1000
(-454…1832)
-9.835…76.373
J
Ni/Cr vs. Cu/Ni
-210…1200
(-346…2192)
-8.095…69.553
K
Ni/Cr vs. Ni/Al
-270…1372
(-454…2501.6)
-6.458…54.886
N
Ni/14.2%Cr/1.4%Si
vs. Ni/4.4%Si/
0.1%Mg
-270…1300
(-454…2372)
-4.345…47.513
R
Pt/13%Rh vs. Pt
-50…1768
(-58…3214.4)
-0.226…21.101
S
Pt/10%Rh vs. Pt
-50…1768
(-58…3214.4)
-0.236…18.693
T
Cu vs. Cu/Ni
-270…400
(-454…752)
-6.258…20.872
Cold junction compensation
Rockwell Automation 871A-TS4CJC-DM, 871A-TR4CJC-DM
Cold junction compensation
range
0…70 °C (32…158 °F) for 302 type thermistors
Thermistor types supported
Thermometrics MF65F302V/W or DC95F302V/W
Input voltage range
±78 mV, 1 mW
Accuracy
0.1% Full Scale @ 25 °C (77 °F)
Accuracy drift with
temperature
30 ppm % Full Scale /°C @ 25 °C (77 °F)
Calibration
Factory calibrated. Calibration is also supported through
RSLogix 5000.
Common mode rejection rate
120 dB @ 50/60 Hz
Normal mode rejection rate
100 dB @ 50/60 Hz
Sample Rate Filters
(1)
50 Hz
60 Hz
250 Hz
500 Hz
(1) Sample Rate/Notch Filter Frequency, selectable per channel.
Input Specifications – 1732E-IR4IM12R
Attributes
Value
Number of inputs
4, isolated
Resolution, min
16 bits
Input Specifications – 1732E-IT4IM12R
Attributes
Value