Appendix C Module Tag Definitions

I.CJData

INT

The cold junction sensor temperature in counts where -32,768 counts is 0 °C (32 °F) and 32,767 counts is 86 °C (186
°F).

Input Tags (1732E-IT4IM12R)

Tag Name

Data Type

Definition

Configuration Tags (1732E-IT4IM12R)

Tag Name

Data Type

Definition

C.Ch0CJCMode
C.Ch1CJCMode
C.Ch2CJCMode
C.Ch3CJCMode

SINT

See

Cold Junction Compensation (CJC) Mode on page 39

.

C.CJCModeIndependent

SINT

See

Cold Junction Compensation (CJC) Mode on page 39

.

C.Ch0LEngineering
C.Ch1LEngineering
C.Ch2LEngineering
C.Ch3LEngineering

INT

One of four points used in scaling. The low engineering helps determine the engineering units the
signal values scale into. The low engineering term corresponds to the low signal value. The scaling
equation used is as follows:

C.Ch0HEngineering
C.Ch1HEngineering
C.Ch2HEngineering
C.Ch3HEngineering

INT

One of four points used in scaling. The high engineering helps determine the engineering units the
signal values scale into. The high engineering term corresponds to the high signal value. The scaling
equation used is as follows:

C.Ch0AlarmDisable
C.Ch1AlarmDisable
C.Ch2AlarmDisable
C.Ch3AlarmDisable

SINT

Disables all alarms for the channel:
0 - Alarms are not disabled
1 - Alarms are disabled

C.Ch0LimitAlarmLatch
C.Ch1LimitAlarmLatch
C.Ch2LimitAlarmLatch
C.Ch3LimitAlarmLatch

SINT

Enables latching for all four process alarms: low, low low, high and high high. Latching causes the
process alarm to remain set until an unlatch service is explicitly sent to the channel or alarm.

C.Ch0NotchFilter
C.Ch1NotchFilter
C.Ch2NotchFilter
C.Ch3NotchFilter

SINT

Configures the channel’s notch filter settings.
See

Notch Filter on page 37

for list of valid input values.

C.Ch0SensorType
C.Ch1SensorType
C.Ch2SensorType
C.Ch3SensorType

SINT

Configures the channel’s sensor type settings.
See

Sensor Type on page 36

for list of valid sensor types.

C.Ch0DigitalFilter
C.Ch1DigitalFilter
C.Ch2DigitalFilter
C.Ch3DigitalFilter

INT

A non-zero value enables the filter. The value serves as a time constant in milliseconds that can be
used in a first order lag filter to smooth the input signal.

C.Ch0LAlarmLimit
C.Ch1LAlarmLimit
C.Ch2LAlarmLimit
C.Ch3LAlarmLimit

INT

The low alarm trigger point. This value causes the Ch<0...3>LAlarm bit to trigger when the input signal
moves beneath the configured trigger point, in engineering units.

Data =

(Signal-LowSignal)(HighEngineering-LowEngineering)

High Signal - Low Signal

+ Low Engineering

Data =

(Signal-LowSignal)(HighEngineering-LowEngineering)

High Signal - Low Signal

+ Low Engineering