Rockwell Automation 1732E-IR4IM12R ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD User Manual
Page 55

Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
47
Calibrate Your Modules Chapter 5
6.
After clicking Start Calibration, a warning dialog appears notifying you of
the risk involved in calibrating an active system and gives you the option to
quit.
If at least one channel has been selected and there is a mismatch between
the device in the RSLogix 5000 I/O Configuration and the actual physical
device, another warning dialog comes up. It informs you that this is
dangerous with an active system and there is a mismatch. This message box
gives you an option to quit. Help is provided to you more information.
From the Danger dialog, for a module not currently used for control, click
OK to continue.
7.
The Input Calibration - Low Value dialog appears.
Set the calibrator for the low reference and apply it to the module.
Click Next to start low reference calibration.
TIP
If several channels have been selected for calibration with One At a Time
option enabled, only one channel will appear in the list at the first round
(low reference and high reference) of calibration.
TIP
If calibration is configured to be done In Groups, the Low Value dialog
box shows all the channels enabled for calibration.