Sensor type – Rockwell Automation 1732E-IR4IM12R ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD User Manual
Page 44

36
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Chapter 4 Configurable Features for the Thermocouple and RTD Input Modules
Configurable Options and
Their Effect on the
Channels
The following features affect the four input channels for the Thermocouple and
RTD Input modules.
Unless otherwise specified, the following features apply to both
1732E-IT4IM12R and 1732E-IR4IM12R modules.
Sensor Type
This set of bits allows you to select one of nine types for the thermocouple
module or one of ten RTD types.
The following sensor type options are available for the Thermocouple and RTD
modules.
Sensor Type
Temperature Units
Digital Filter
Notch Filter
(1)
CJC Enable
(2)
CJC Offset
(2)
CJC Mode
(2)
(1) Notch Filter can be set per channel on the Thermocouple module, and module-wide on the RTD module.
(2) Available on the 1732E-IT4IM12R Thermocouple module only.
Supported Sensor Types – 1732E-IT4IM12R
Type
Material
Temperature
Range °C (°F)
Voltage
Range (mV)
B
Pt /30% Rh vs. Pt/5% Rh
40…1820 °C (104…3308 °F)
0…13.820
C
W/5% Re vs. W/26% Re
0…2320 °C (32…4208 °F)
0…37.107
E
Ni/Cr vs. Cu/Ni
-270…1000 °C (-454…1832 °F)
-9.835…76.373
J
Ni/Cr vs. Cu/Ni
-210…1200 °C (-346…2192 °F)
-8.095…69.553
K
Ni/Cr vs. Ni/Al
-270…1372 °C (-454…2501.6 °F)
-6.458…54.886