Clamp/limit alarms, Data echo, Clamp/limit alarms data echo – Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules User Manual
Page 97

Rockwell Automation Publication 1756-UM540A-EN-P - May 2014
97
1756-OF8I Isolated Analog Output Module
Chapter 5
Clamp/Limit Alarms
This function works directly with clamping. When a module receives a data value
from the controller that exceeds clamping limits, it applies signal values to the
clamping limit but also sends a status bit to the controller notifying it that the
value sent exceeds the clamping limits.
With the previous example, if a module has clamping limits of 8V and -8V but
then receives data to apply 9V, only 8V is applied to the screw terminals and the
module sends a status bit back to the controller informing it that the 9V value
exceeds the module’s clamping limits.
To see where to set clamp and limit alarms, see
Data Echo
Data Echo automatically multicasts channel data values that match the analog
value that was sent to the module’s screw terminals at that time.
The 1756-OF8I module returns a status word that represents the value sent to it
by the controller. The echoed value is indicated in input tag
I.Ch[x].Data and is
represented in Engineering Units.
Fault and status data are also sent. This data is sent at the RPI.