Isolated Analog I/O Module Tag Definitions
Appendix A
Ch[x].FaultFinalState
REAL
Value to which the channel changes if the following
events exist:
• Connection is lost
• Time defined by the C.Ch[x].FaultValueStateDuration
tag has been exceeded
Any
0.0 = default
Ch[x].ProgValue
REAL
Value to which the channel changes if the following
events exist:
• Module transitions to Program mode
• C.Ch[x].ProgMode tag is enabled
Any
0.0 = default
Ch[x].LowSignal
REAL
Signal value that lets you scale signal units (V, mA) into
Engineering Units.
Corresponds to the C.Ch[x].LowEngineering tag. That is,
this tag’s value is scaled to the lowest Engineering Unit.
Any value less the
C.Ch[x].HighSignal tag value.
Current input type: 4.0 = default
Voltage input type: -10.0 = default
Ch[x].HighSignal
REAL
Signal scaling value that lets you scale signal units (V, mA)
into Engineering Units.
Corresponds to the C.Ch[x].HighEngineering tag. That is,
this tag’s value is scaled to the highest Engineering Unit.
Any value greater than the
C.Ch[x].LowSignal tag value
Current input type: 20.0 = default
Voltage input type: 10.0 = default
Ch[x].LowEngineering
REAL
Low engineering scaling point
Corresponds to the C.Ch[x].LowSignal tag value.
Any lower than the
C.Ch[x].HighEngineering tag
Default values:
• 0.0 for current
• -10.0 for voltage
Ch[x].HighEngineering
REAL
High engineering scaling point
Corresponds to the C.Ch[x].HighSignal tag value.
Any higher than the
C.Ch[x].LowEngineering tag
Default values:
• 100.0 for current
• 10.0 for voltage
Ch[x].LowLimit
REAL
LowLimit setpoint below which the output cannot go
when Clamping is enabled.
Any lower than the HighLimit
0.0 = default
Ch[x].HighLimit
REAL
HighLimit setpoint above which the output cannot go
when Clamping is enabled.
Any higher than the LowLimit
0.0 = default
Ch[x].Offset
REAL
Compensates for any known error on the sensor or
channel to which the sensor is connected. The value is set
in signal units.
Any
(We recommend that you use a
small value.)
0.0 = default
Table 26 - 1756-OF8I Module - Configuration Tags
Tag Name
Size
Definition
Valid Values