Status indicators for the 1756-of8i module – Rockwell Automation 1756-OF8I ControlLogix Eight-channel Isolated Analog I/O Modules User Manual
Page 159
Rockwell Automation Publication 1756-UM540A-EN-P - May 2014
159
Troubleshoot Your Module
Chapter 9
Status Indicators for the
1756-OF8I Module
The following graphic shows the status indicators used with 1756-OF8I module.
The following table describes the status indicators.
ANALOG OUPUT
ST
FLT
O
K
Indicator
Status
Description
OK
Steady green
The module is in a normal operating state in Run mode.
Flashing green
The module passed internal diagnostics and is not actively controlled or
the connection is open and the controller is in Program mode.
Flashing red
Previously established communication has timed out.
Steady red
Replace the module.
ST
Steady yellow
The channel is operating as expected.
Flashing yellow
The channel is being calibrated.
Off
The channel is not in use or is faulted.
FLT
Off
The channel is operating as expected.
Steady red
• The channel is faulted. Some possible causes of the fault include:
– Triggered clamp alarm
– Wire off detection
– Calibration fault
For more information on these causes see Chapter 5,
Analog Output Module on page 93
Flashing red
The channel is faulted. See the previous row for more information
about faults.